Varicell Filters Technical Specification


Varicell construction features: (all data, performance, and part numbers based on actual filter size of 592 x 592 x 292mm). Galvanised steel cell sides with media retaining flanges and welded header. Varicell may be specified for either upstream or downstream service.

SUPPORTED RIGID MEDIA PACK: Up to 14m2 of pleated media surface area. Maximum surface area provides savings in operating costs and also reduced pressure drop.

MOISTURE RESISTANT: Ultrafine microglass fibre paper media.

MEDIA SEPARATORS: Crimped aluminium.

GLASS PACKING SEALANT: For media behind retaining flanges, absorbs shock yielding to motion, yet maintains a positive seal. Eliminates shearing of media common with glued construction.

EFFICIENCY RANGES: Uperfine spun glass fibre pleated media, 60-65%, 80-85% 90-95%.

UNAFFECTED BY VARIABLE AIR VOLUME: Well suited to various volume systems.

OTHER SIZES AND CONSTRUCTION AVAILABLE: E.g. stainless steel high temperature model, no header frame. 150mm deep model and none standard sizes available on request.

PERIPHERAL HEADER: Available in 20, 22 or 25mm with single or double header for extra support.

RATED AIR VOLUME: 3400 m3/hour for a 592 x 592 x 292mm size.

INITIAL RESISTANCE: F6:125pa, F7:138pa, F8:150pa, F9:163pa, H10-180pa.

FINAL RESISTANCE: F6:300pa, F7:325pa, F8:350pa, F9:375pa, H10-400pa.

MAXIMUM TEMPERATURE: 250°C